Technical Parameter:
Storage volume(L) |
70 |
Agent type |
CO² |
Agent filling weight(Kg) |
42 |
Density of the filled agent |
≤0.60Kg/L |
Storage pressure under 20°C (M pa) |
5.7 |
Max. working pressure (M pa) |
12.4 |
Discharge time(S) |
≤60 |
Starting voltage / Current |
DC24V/1.2A |
Temperature range of storage room |
0°C ~ +50°C |
Humidity requirement of storage room |
≤97% |
Extinguishing way |
Total or partial flooding |
Starting delay time |
0 ~ 30S adjustable |